Nothing sent to a server
One published sizing expression

Size round and rectangular HVAC ducts from CFM and friction. Enter your numbers and get an instant result.

Type an airflow in cubic feet per minute and a friction rate in inches of water column per hundred feet, and this page returns three figures for a round duct: a diameter in whole inches, the air velocity that diameter produces, and a rectangular equivalent with a fixed ten-inch height.

The arithmetic runs entirely in the tab. The diameter is 2.42 times the airflow divided by the square root of the friction rate, raised to the power 0.38, then rounded up to the next whole inch; velocity is the airflow divided by that circle's area; and the rectangle's width is the rounded diameter squared, divided by ten and rounded up.

The page is a single-point estimate from one published sizing expression, not a duct design. It never asks for duct material, fitting losses, a noise criterion or a local code, so a figure here is a starting number to check against a ductulator and an engineer's review.

What the three outputs mean

The round diameter is the expression's answer, rounded up so the velocity is computed from the size actually shown rather than from an unrounded interior value. The render still shows the FPM figure one decimal place.

The rectangular equivalent keeps a height of ten inches and takes a width of diameter squared divided by ten. That matches the round duct's cross-sectional area, which is the only property it matches.

  • Diameter: 2.42 times (CFM divided by the square root of friction) to the power 0.38, rounded up
  • Velocity: CFM divided by the area of the rounded diameter, in feet per minute
  • Rectangle: ten inches high, width from the diameter squared divided by ten

Where the estimate stops

A real duct calculation adds the pressure loss of every fitting, the length of every run and the terminal device, and it checks the result against a noise criterion. This page models none of those, so a single branch can look fine here and still be wrong in a system.

The rectangular figure is especially easy to misread: equal area is not equal friction. A designer choosing a rectangular duct normally works from an equal-friction chart or a velocity target, which is a different calculation from the one on this page.

How to use the system parameters

Type the Airflow Volume in CFM and the Friction Rate in inches of water column per hundred feet into the System Parameters panel; the Specifications panel answers at once with the Round Duct Diameter in whole inches, the Air Velocity that diameter produces, and the Rectangular Equivalent with its fixed ten-inch height.

Read the three figures as one published sizing expression: 2.42 times airflow over the square root of friction to the 0.38, rounded up, never as a duct design. The page never asks for fittings, runs, noise limits or local codes, so check the number against a ductulator and an engineer review.

What to Expect

Best for

  • A quick first diameter for a residential branch before checking a ductulator
  • Seeing how airflow and friction push the size in opposite directions
  • Getting a rectangle width for a fixed ten-inch ceiling void

Not ideal for

  • A permit drawing or an installation that must satisfy a mechanical code
  • Systems where fittings, dampers or long runs dominate the pressure loss
  • Sizing for a noise target, since the page does not model sound

What this tool keeps

  • The same three figures for the same two inputs on every reload
  • A diameter rounded up to a whole inch, so the velocity matches the size shown
  • A rectangular equivalent that always keeps the ten-inch height

What may need cleanup

  • The round diameter, which the expression can push well above a normal residential size at a low friction rate
  • The rectangular width, which matches area at a fixed height rather than friction
  • The friction rate itself, which should come from a design chart rather than a guess

Common errors

  • Reading the rectangular width as an equal-friction equivalent when only the area is matched
  • Leaving friction at the default and expecting a size for a different design
  • Entering zero or a negative number, which blanks the result instead of warning

Example use cases

  • A rough size while laying out a basement supply run
  • A teaching example of how friction changes duct diameter
  • A sanity check against a contractor's quoted size

Sample input

1000 CFM at a friction rate of 0.1 inches of water column per 100 feet, the two values the page opens with.

Sample output

A 52-inch round diameter, an air velocity of 67.8 FPM and a rectangular equivalent of 271 inches by 10 inches.

Who this is for

  • Homeowners comparing a contractor's quoted duct size
  • Students learning the friction-rate relationship
  • Technicians who need a first figure before opening a ductulator

Frequently asked questions

What three figures does the duct sizer return?

A round diameter in whole inches, the air velocity that diameter produces, and a rectangular equivalent with a fixed ten-inch height.

Is the result a permit drawing?

No. It is an estimate for a round duct and does not satisfy a mechanical code.

Why does a low friction rate produce an unusually large diameter?

The expression can push the round size above a normal residential diameter at a low friction rate; the friction rate should come from a design chart.